            Mobily Tier-2 Maddinah is located in the area Maddinah, Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


            Address:
            Mobily
            Madinah
            11423 Sultana
            Maddinah, Saudi Arabia

            » Request quote
            » Visit website

            Click here to find other data centers
            owned and operated by Mobily.


            Profile
            Tenants
            Connectivity
            Request quote
            Office space
            Rack Cabinets
            Dedicated Servers
            Suites
            Footprints
            Virtual Servers
            Cages
            Hosting of individual servers
            Remote Hands

            Profile


            MECHANICAL SYSTEM
            --------------------------

            a-Cooling System: Refrigerant cooling system.

            b-CRAH Redundancy: N+1, Data Center equipment demand cooling load is 1000 W/m2

            c-Fuel Oil: Fuel Oil Generator fuel oil storage 48 hours capacity

            d-Site Scan: Computerized Building Management System M&E equipment verification and management

            ELECTRICAL SYSTEM
            -------------------------
            a-Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.

            b-Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.

            c-Generator: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1.

            d-Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel.

            c-UPS: Parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center.

            d-Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

            e-Security System: IP access control system and Analog CCTV system


            Mobily Tier-2 Maddinah Pricing/Quotes


            If you are interested in receiving a quote for Mobily, please try our free quote service.

            Copyright © Data Center Map - Sitemap
            Your guide to colocation data centers, managed hosting, cloud servers etc.
            日本一本道不卡视频在线大全
              1. <code id="jjto2"><nobr id="jjto2"><sub id="jjto2"></sub></nobr></code>
                <big id="jjto2"><em id="jjto2"></em></big>

                    <strike id="jjto2"></strike>

                    <tr id="jjto2"></tr>